Boiler House CCTV Specification: Reading the Gauge Glass, Heat Zones and the Boilers Act 2025 (India)
Can a camera read a boiler water-level gauge glass from outside the 10 m attendant zone? Yes for the water line: a CP Plus 2.7–13.5 mm varifocal set to 28° puts about 359 px/m on the glass from 15 m, roughly 7 pixels across a 20 mm glass. It does not replace the attendant: the Boiler Attendants' Rules, 2025 deem a person in charge only "when he is within ten meters" of the boiler. A one-boiler house with a thermic fluid heater and fuel yard needs about 7 cameras.
Last checked: 15 Oct 2026. The layout and the 20 mm glass width are worked assumptions; legal text, densities, lens angles and temperatures are sourced.
Verified against
- The Boilers Act, 2025 (Act 12 of 2025, Gazette of India, 4 April 2025), full text.
- Boiler Attendants' Rules, 2025, G.S.R. 721(E), 29 September 2025, and Boiler Operation Engineers' Rules, 2025, G.S.R. 705(E), 22 September 2025 (Gazette copies hosted by the Maharashtra Directorate of Steam Boilers).
- IEC 62676-4:2014 pixel densities, quoted in the foreword of IEC 62676-4:2025 (STN EN IEC 62676-4:2026 preview); level wording from Axis, Pixel density based on IEC 62676-4:2014.
- CP Plus datasheets: CP-UNC-TA41L3C-Q, CP-UNC-TA41L6C-Q, CP-UNC-TA21L6C-Q, CP-UNC-TC41ZL6C-VMD-LQ.
- Movitherm, TSF-AC air-cooled housing datasheet.
- Hikvision, H.264(5) recommended bit rate sheet (archived copy); IMD, heat-wave definitions.
- Checked 15 Oct 2026.
What the boiler law says about cameras
No camera, CCTV, video or remote-monitoring requirement appears in the Boilers Act, 2025, the Boiler Attendants' Rules, 2025 or the Boiler Operation Engineers' Rules, 2025 (full texts searched, checked 15 Oct 2026). The Act repealed the Boilers Act, 1923 (section 45(1)); rules and regulations made under the old Act apply only until new ones are made (section 45(2)(a)).
What the law does fix is presence. Under rule 7(1) of the Attendants' Rules, a person in charge "shall be deemed to be in direct and immediate charge" of a boiler "when he is within ten meters" of it. For a Boiler Operation Engineer, rule 7(1) of the Operation Engineers' Rules sets "within hundred meters". An attendant may be relieved by a first-class attendant for at most two periods a day, totalling no more than two hours (Attendants' Rules, rule 7(2)). A boiler counts as "in use" whenever there is fire in the furnace, including banked fire (rule 8(1)).
A boiler-front camera can show whether someone stood in that 10 m zone; it replaces no certificate or Inspector. The owner must still report any accident in writing to the Inspector within 24 hours (Act, section 23(1)).
A thermic fluid heater heats oil, not water into steam. The Act's definition of "boiler" is a pressure vessel "in which steam is generated" (section 2(c)), so a heater that raises no steam reads as outside it; confirm with your state Directorate of Boilers.
Reading the gauge glass
Here pixels per millimetre matter more than scene width. Density follows from horizontal pixels, slant distance and printed HFOV (the DORI explainer shows the arithmetic); divide px/m by 1,000 for px per mm.
Worked for a 20 mm wide glass (assumption) and 2688-pixel CP Plus cameras at their printed HFOV:
| Camera, HFOV | Slant distance (m) | Scene width (m) | px/m | px per mm | Pixels across 20 mm glass |
|---|---|---|---|---|---|
| TC41ZL6C-VMD-LQ, wide end 97° | 5.8 | 13.2 | 204 | 0.20 | 4 |
| TC41ZL6C-VMD-LQ, set to 60° | 5.8 | 6.7 | 399 | 0.40 | 8 |
| TC41ZL6C-VMD-LQ, tele end 28° | 10 | 5.0 | 539 | 0.54 | 11 |
| TC41ZL6C-VMD-LQ, tele end 28° | 15 | 7.5 | 359 | 0.36 | 7 |
| TA41L6C-Q, 6 mm, 49° | 10 | 9.1 | 295 | 0.30 | 6 |
| TA41L3C-Q, 3.6 mm, 78° | 10 | 16.2 | 166 | 0.17 | 3 |
How to read the table:
- 250 px/m is the planning floor (IEC 62676-4:2014 Identify, used as a reading level, our assumption). The 3.6 mm bullet at 10 m falls short.
- Zoom buys distance. At 28° the varifocal holds 359 px/m from 15 m, so it can sit back from the drum and the blow-down path.
- A level line, not a scale. Six to eleven pixels across the glass shows where the water sits, not the graduations.
- Light it, and turn IR off. Built-in IR bounces off steam and the glass face.
Why this does not replace the attendant: the 10 m rule puts a person where they can act on the boiler. Footage from 15 m shows the level and whether anyone stood in the zone; it cannot act on a low-water alarm. Check positions in the lens and DORI calculator.
Task per view → pixel density
| View | Task | Level | px/m on target |
|---|---|---|---|
| Water gauge glass, drum level | Where the water column sits in the glass | Identify (used as a reading level) | 250 |
| Boiler control panel | Pressure gauge position, alarm lamps, controller display | Identify or higher | 250+ |
| Fuel feeding (hopper, screw feeder or firing door) | Feeder running or empty, fuel being charged | Recognise | 125 |
| Ash handling, ash pit | Ash removed or piling up, trolley movement | Observe to Recognise | 62.5–125 |
| Boiler-front floor | Attendant present in the 10 m zone | Observe | 62.5 |
| Thermic fluid heater front | Burner area, controller, people at the unit | Recognise | 125 |
| Fuel yard | Pile size, unloading, loader movement | Observe | 62.5 |
Densities are the IEC 62676-4:2014 values. Vendor DORI runs a little longer than the arithmetic: CP Plus prints Recognise at 24.8 m for the TA41L6C-Q, while its 49° HFOV gives 23.6 m. Plan on the lower figure.
Heat-zone map: where each camera class survives
Place each camera by the zone it sits in, not the view it needs; zoom covers the gap.
| Zone | What drives the heat or fouling | Camera class that fits | Rule |
|---|---|---|---|
| Fuel yard (outdoors) | Sun and ambient; one IMD heat-wave criterion is a maximum of 45 °C or more | Standard bullet, −40 to +60 °C (TA41L6C-Q) | Shade the housing; it leaves 15 °C of headroom on a heat-wave day |
| Ash pit, fuel feed | Ash and fuel dust on the window, some radiant heat | Standard bullet, IP67 | Clean the window on a schedule, or use a housing with an air jet |
| Boiler-front floor, control panel, thermic fluid heater front | Radiant heat from the boiler shell and heater | Standard bullet or the varifocal (−30 to +60 °C) | Log the temperature at the mount through a May afternoon before buying |
| Blow-down and safety-valve plume | Steam; the CP Plus sheets say "non-condensing" | None of the cameras here | Keep out of the vent path, upwind of leaks |
| Above the drum or the flue duct | Rising radiant heat from drum and flue | Cooled housing: Movitherm TSF-AC, up to 100 °C (visible camera), AISI316L, IP66/67, vortex-tube cooling, window air jet | Better: don't mount here; zoom in from a cooler wall |
The cooled housing needs a filtered compressed-air line (Movitherm lists a 20/5/0.1 µm filter set). If coal is milled on site, get the hazardous-area classification before any camera goes near the mill.
Worked spec for a 1-boiler house
Assumption: one solid-fuel IBR boiler, one thermic fluid heater, a 20 × 15 m house, a 40 m fuel yard.
| View (cameras) | Model, lens | Pixels × HFOV | Mount (assumption) | Scene width (m) | px/m | Meets |
|---|---|---|---|---|---|---|
| Gauge glass (1) | CP Plus TC41ZL6C-VMD-LQ, 2.7–13.5 mm set to ~60° | 2688 × 60° | 3 m high, 5 m out | 6.7 | 399 | Identify |
| Control panel (1) | CP Plus TA41L6C-Q, 6 mm | 2688 × 49° | 2.5 m high, 2 m out | 2.9 | 921 | Identify |
| Fuel feeding (1) | CP Plus TA41L3C-Q, 3.6 mm | 2688 × 78° | 4 m high, 7 m out | 13.1 | 206 | Recognise |
| Ash pit (1) | CP Plus TA21L6C-Q, 6 mm | 1920 × 54° | 4 m high, 14 m out | 14.8 | 129 | Recognise |
| Boiler-front floor (1) | CP Plus TA41L3C-Q, 3.6 mm | 2688 × 78° | 5 m high, 10 m out | 18.1 | 148 | Recognise |
| Thermic fluid heater (1) | CP Plus TA41L3C-Q, 3.6 mm | 2688 × 78° | 3.5 m high, 6 m out | 11.3 | 239 | Recognise |
| Fuel yard (1) | CP Plus TA41L6C-Q, 6 mm | 2688 × 49° | 6 m high, 24 m out | 22.6 | 119 | Observe |
If the boiler front runs hot at 5 m, move the gauge-glass camera back to 15 m and zoom to 28° (table above).
Cameras per unit or per N metres (rule of thumb, assumption):
- Per boiler: gauge glass, panel, fuel feeding, boiler-front floor.
- One per thermic fluid heater and one per ash pit.
- Fuel yard: the TA41L6C-Q holds Observe out to 47.2 m, where it spans 43 m. Plan one per ~40 m of yard frontage.
Total: 7. Recording runs about 44.2 GB per 4 MP camera per day at 4,096 Kbps H.265 (Hikvision bit rate sheet, 25 fps); size the disk for your retention with the NVR days table. The loading dock spec uses the same method.
Ratings that matter here
| Item | Boiler-house spec | Source |
|---|---|---|
| Humidity | "≤95%(RH), non-condensing" (TA41L3C-Q) | CP Plus datasheet |
| Ingress | IP67 on all four models | CP Plus datasheets; see the IP/IK guide |
| Impact | "IK10 (optional)" on TC41ZL6C-VMD-LQ only; the bullets list no IK rating | CP Plus datasheets |
| Low light, IR | Colour 0.03 [email protected], IR 30 m (TA41L3C-Q); 0.001 [email protected], IR 60 m (TA41L6C-Q, TA21L6C-Q) | CP Plus datasheets |
Set IR off on the gauge-glass and panel cameras and light those views instead. Fire-exit and escape-route cameras are a different job, covered in fire and emergency exit monitoring.
When to call the installer / what to ask the vendor
Ask for the printed HFOV at your focal length, the upper operating temperature, humidity and IK ratings. At handover, zoom the gauge-glass camera and check on the NVR screen, day and night, that the level line is visible and the glass is as many pixels wide as the table above gives for that distance.
A boiler trip stops steam to the whole plant. Mama reads a factory's existing cameras over RTSP/ONVIF and tells the owner in plain language how long machines stood idle yesterday (askthemama.com). Leave an email or phone in the form below.
FAQ
Can a CCTV camera read a boiler water level gauge glass? It can show where the water line sits if it puts about 250 px/m or more on a lit glass. A varifocal at 28° does that from 15 m (359 px/m, about 7 pixels across a 20 mm glass). That is a level line, not a scale reading.
Does a gauge-glass camera replace the boiler attendant? No. The Boiler Attendants' Rules, 2025 deem a person in charge only when within ten metres of the boiler (rule 7(1)). A camera can show whether someone was in that zone; it cannot act on the boiler.
Is CCTV mandatory in a boiler house in India? Not in the 2025 boiler law texts. The Boilers Act, 2025 and the 2025 Attendants' and Operation Engineers' Rules contain no camera requirement (checked 15 Oct 2026).
Which CCTV camera works near a boiler? Standard bullets such as the CP Plus models above are rated to +60 °C. Above the drum or flue, use a cooled housing: the Movitherm TSF-AC is rated up to 100 °C for a visible camera. Better still, mount on a cooler wall and zoom.