Thermal Cameras for Early Fire Detection in a Factory: What Works, What India's Code Accepts, ₹

By The Mama Editorial Team · Factory-floor cameras, India compliance & operations

Can a thermal camera be your factory's fire detector in India? Not on its own. As of 15 Oct 2026, IS 2189:2026 lists video fire detectors (IS/ISO 7240-29) as an alarm component, but no thermal hotspot camera. NBC 2016 Part 4 does not mention video detection at all. A radiometric thermal camera is an early-warning layer on top of the certified system.

Last checked: 15 Oct 2026. The godown layout is an assumption.

Verified against

Thermal, video analytics or a certified detector: by application

Application Radiometric thermal camera Flame/smoke analytics on normal CCTV Detector type IS 2189:2026 describes Limitation
Cotton or yarn-waste godown Alarms on a pile surface heating, by threshold or rate of rise (Axis WP §3.3) Needs visible smoke or flame and light Flame detectors suit "high-ceiling, open-spaced buildings such as warehouses" (§5.1.4.3) Sees only the surface facing the lens, not inside a bale
Scrap and waste piles Vendor names recycling sites and waste piles (Axis WP §3.3.1) Daylight only, if smoke is visible Flame detectors for outdoor areas where draughts keep smoke from detectors (§5.1.4.3) Sun-heated metal and hot incoming loads look like hotspots
Coal, biomass or husk yard Vendor names coal piles and silos (Axis WP §4) Smoke is hard to separate from dust Spark/ember detectors on a duct or conveyor (§5.1.4.1) Fog and rain reduce accuracy (Axis WP §3.2)
LT panels, transformers Vendor names switchgear and transformers (Axis WP §4) Little use on a closed steel panel Smoke detection per NBC 4.9 Shiny metal (emissivity 0.6 or lower) reads wrong (Axis WP §2.3)
Battery storage Watches cabinet and rack surfaces Smoke appears late Classify the area first: explosion-proof CCTV and PESO Cells sit inside cabinets, out of the lens's line of sight

The mapping is our engineering reading.

Radiometric vs non-radiometric: same sensor, different job

Axis puts it plainly: "temperature-calibrated thermal cameras, called thermometric cameras, can measure absolute temperatures, while surveillance-optimized thermal cameras show relative temperatures" (Q1961-TE datasheet, checked 15 Oct 2026). Only the radiometric kind can alarm at a set temperature.

Spec (Axis datasheets, checked 15 Oct 2026) AXIS Q1961-TE (radiometric) AXIS Q1951-E (non-radiometric)
Sensor (pixels) 384 × 288, 17 μm 384 × 288, 17 μm
Spectral range (μm) 8–14 8–14
Object temperature range (°C) −40 to 350 no thermometry
Accuracy ±5 °C below 120 °C; ±15% above not applicable
Fire analytic Early fire detection none listed
Lenses, HFOV (°) 7 mm 55°; 13 mm 28° 7 mm 55° to 35 mm 10.5°
Operating temperature (°C) −40 to 60 −40 to 60

A threshold alarm triggers on the highest, lowest or average temperature in a polygon. A rate alarm triggers if the temperature "increases or decreases too quickly" (Axis white paper §3.3.1).

Axis early fire detection filters out moving hot objects, but an object still for more than 30 seconds is treated as static and can alarm (§3.3.2). A forklift with a hot engine, parked in view, can then alarm.

What India's code says

NBC 2016 Part 4 does not mention video or thermal-imaging detection (full text searched, checked 15 Oct 2026). Clause 2.4 defines automatic detection as "automatically detecting smoke, heat or fire". Clause 4.9(g) requires the detection system to follow "accepted standards [4(15)]": IS 2175 and IS/ISO 7240-5 (heat), IS/ISO 7240-7, -15 and IS 11360 (smoke), IS/ISO 7240-11 (manual call points). Detector selection follows "good practice [4(16)]", listed as IS 2189:2008. The only CCTV mention, clause 3.4.12(b), lets CCTV be monitored from the fire command centre.

For most factories the NBC table is not final. Table 7 Note 17 says the Group G figures "are for small scale industry units"; for other industries requirements are worked out from Indian Standards "and also in consultation with the local fire authorities".

IS 2189:2026 now names video fire detectors. Table 1 lists "Video fire detectors" under IS/ISO 7240 Part 29 (2017), and the inspection table checks "video image smoke and fire detectors" quarterly (IS 2189:2026, checked 15 Oct 2026).

Two clauses rule out the shortcut. Clause 4.1: alarm equipment and cables "shall be independent of any other system or cables, and shall not be shared with any other system". A camera on your CCTV LAN and NVR fails that. The foreword adds that automatic detection is "not considered a substitute for automatic sprinklers".

No thermal hotspot detector type appears in IS 2189:2026 Table 1 (checked 15 Oct 2026). The NOC side is covered in what fire NOC inspectors look for.

Where the standards differ abroad

Scheme What is recognised Source (checked 15 Oct 2026)
India, IS 2189:2026 Video fire detectors to IS/ISO 7240-29:2017 Table 1
France, CNPP Cert. "Thermal camera heat detection systems" as a certified category; Hikvision DS-2TD2137T, 2167T, 2637T, 2667T, 4137T, 4167T, effective 30 Mar 2023, validity ended 29 Mar 2026 on this copy CNPP 32.20.221, 33.20.221

The CNPP certificates describe the systems as "associable with power supply compliant with EN54-4", the European fire-alarm power-supply standard. Where a thermal camera counts as a heat detector, it is a certified model with a fire-grade supply, not an off-the-shelf CCTV camera.

Sizing: how far can the camera see a hotspot

Axis recommends a monitored object cover at least 10 × 10 pixels of the 384 × 288 sensor (Q1961-TE datasheet). With R = 384 px:

d_max = s × R ÷ (10 × 2 × tan(HFOV/2)), where s is hotspot size in metres.

Hotspot size (m) 7 mm, 55° HFOV: max distance (m) 13 mm, 28° HFOV: max distance (m)
0.1 3.7 7.7
0.3 11.1 23.1
0.5 18.4 38.5
1.0 36.9 77.0

Worked example (assumed layout): a 40 m × 20 m cotton-waste godown, camera on a short wall. A 0.3 m hotspot 40 m away is beyond both lenses; the 13 mm reaches 23.1 m. Two 7 mm cameras, one per 20 m half, cover the full width (20.8 m at 20 m) and catch hotspots of about 0.54 m (20 ÷ 36.9). For 0.3 m at 20 m the 13 mm qualifies, but it covers only 10 m of width there, so plan four. Check positions in the lens and DORI calculator.

Certified models and ₹. Mama's dataset of 2,229 primary STQC ER and BIS CRS rows contains zero thermal or bi-spectrum models (name and type search; checked 15 Oct 2026). Check any quoted model in the Certified CCTV Finder. No INR price list for fixed thermal cameras was found from Axis or Hikvision India (checked 15 Oct 2026); budget from written quotes.

What breaks in a factory

When to call the installer / what to ask the vendor

  1. "Is this model radiometric? Send the datasheet line with temperature range and accuracy."
  2. "What is the smallest hotspot your design catches at our farthest point?" Ask for the 10 × 10 pixel arithmetic.
  3. "Is the fire analytic certified by any fire body for this model and firmware?" Ask for the certificate.
  4. "How does the alarm reach a person at 2 a.m.?" Relay into the fire panel input, a siren, or only an app?

Where Mama fits

Mama reads existing cameras over RTSP/ONVIF to report machine idle time to the owner. It is not a fire detector. For a camera plan, leave an email or phone in the form below. More at askthemama.com.

FAQ

Can a thermal camera detect fire before a smoke detector?

For a surface in its view, it can: Axis describes early fire detection as catching "a smoldering fire before it spreads". It cannot see inside a bale or a closed panel. Smoke and heat detectors remain the system NBC 2016 Part 4 clause 4.9 requires.

Is video fire detection approved in India?

IS 2189:2026 lists video fire detectors conforming to IS/ISO 7240-29 as an alarm component, inspected quarterly. They must be independent of any other system (clause 4.1), so analytics on your CCTV NVR does not qualify. Thermal hotspot cameras are not listed (checked 15 Oct 2026).

What is the difference between radiometric and non-radiometric thermal cameras?

A radiometric camera is temperature-calibrated: the AXIS Q1961-TE reads −40 °C to 350 °C, ±5 °C below 120 °C. A non-radiometric camera such as the AXIS Q1951-E shows relative heat for detecting people and vehicles. Only the radiometric kind can alarm at a set temperature.

Last verified 15 Oct 2026 against the vendor and regulator documents listed above. Found an error? Tell Mama in the form below.

Read next
Free · no obligation

Get a camera plan for your floor

Tell Mama about your plant and Mama will come back with how many cameras you need, where they go, and the retention your state expects — sized to your floor, in ₹. Built for Indian factories.

  • How many cameras & exact placement
  • Compliance-ready (BIS/STQC, women's night shift)
  • Honest ₹ estimate — guard vs camera-AI

Mama replies by email or phone — whichever you left. No spam, no obligation.