Explosion-Proof CCTV in Indian Hazardous Areas: Zones, Ex Marking and PESO Approval

By The Mama Editorial Team · Factory-floor cameras, India compliance & operations

Under Rule 106 of the Petroleum Rules, 2002, as amended in 2018 and 2024, a camera in a Zone 1 petroleum area must use an IS/IEC 60079 protection type such as flameproof (Ex d), chosen by EPL. PESO says such equipment needs Chief Controller approval. An IECEx or ATEX certificate alone is not that approval.

Verified against

Zone → what the camera must be

Zone Meaning (IEC / HSE) Rule 106 as amended (2018, 2024) EPL normally required Source
0 Explosive gas present continuously, for long periods or frequently No electric apparatus, except approved intrinsically safe apparatus (IS/IEC 60079-11, -26) where it "cannot be completely excluded" Ga PR 2002, 2024 amdt, Axis
1 Likely in normal operation Flameproof, pressurised, powder-filled, oil-immersed, increased safety, intrinsically safe or encapsulated, to IS/IEC 60079-1/-2/-5/-6/-7/-11/-18; or a pressurised/purged room with cut-off or alarm Gb (or Ga) same
2 Not likely; if it occurs, short-lived Non-sparking (IS/IEC 60079-15) of an approved type, approved trace heating, or any Zone 1 type Gc (or Gb, Ga) same
20 Combustible dust cloud continuously/frequently Not addressed by Petroleum Rules Da HSE, Axis
21 Dust cloud likely occasionally in normal operation Not addressed Db (or Da) same
22 Dust cloud unlikely; short-lived Not addressed Dc (or Db, Da) same

Since 2024, sub-rule 106(3A) says Ex apparatus "shall be" selected by EPL per IS 16724:2018/IEC 60079-14, so the EPL column is now a legal test. Rule 104's Zone 2 wording differs from IEC ("only under abnormal operating conditions or failure or rupture of an equipment"); the Chief Controller's zoning decision "shall be final", and extent follows the Fourth Schedule (R.105).

Decoding an Ex marking

Two markings Honeywell shows for its India-made Ex IP cameras (example, not a recommendation): Ex db IIC T6 Gb (gas) and Ex tb IIIC T80°C Db (dust).

Field Example What it means Source
Protection type db / eb / ia / mb / pxb / tb d = flameproof (contains the explosion), e = increased safety, i = intrinsic safety, m = encapsulation, p = pressurised, t = dust enclosure; letter a/b/c = level Axis poster
Gas group IIA / IIB / IIC IIA propane, IIB ethylene, IIC hydrogen and acetylene; higher group covers lower same
Dust group IIIA / IIIB / IIIC IIIA fibres/flyings, IIIB non-metal dust incl. flour, grain, wood, plastics, IIIC metal dusts same
Temperature class T1…T6 Max surface temp: T1 450 °C, T2 300, T3 200, T4 135, T5 100, T6 85 °C; dust marks a °C figure instead same
EPL Ga/Gb/Gc, Da/Db/Dc Ga→Zone 0, Gb→1, Gc→2; Da→20, Db→21, Dc→22 same
Ambient (Ta) e.g. −40 °C ≤ Ta ≤ +60 °C If not marked, the rated ambient is −20 °C to +40 °C IEC 60079-0:2017 cl.1 Note 1

Selection rule: the camera's maximum surface temperature (T class) must be below the ignition temperature of the gas present; group and EPL must meet or exceed the zone drawing.

What a PESO approval actually is

Where schemes differ: IECEx/ATEX, BIS, PESO

Our interpretation (not legal advice): a paint shop with thinner or a tank farm with Class A/B petroleum is squarely inside. A solvent room using only non-hydrocarbon solvents, or a flour mill with dust only, may fall outside Rule 106's text. That does not make an ordinary camera acceptable: the zone drawing still demands the matching EPL, and other rules may apply. Confirm with your PESO circle office and a competent hazardous-area engineer before buying.

What breaks in a factory

What to ask the vendor

  1. The PESO approval letter: number, equipment reference, zone, gas group, validity.
  2. Does the nameplate show that reference number?
  3. The IECEx/ATEX certificate the letter cites, and its Ta range.
  4. For India-made flameproof housings: the BIS CM/L number, if any.
  5. Which cable glands are approved with it, and who in India services it.

Ordinary cameras outside the zones, and chemical-plant permits and incidents, are covered in chemical-plant cameras and PESO and the tender specification template.

Where Mama fits

Ex certification is outside Mama's scope. It reads existing cameras over RTSP/ONVIF — including ordinary ones watching solvent stores and mixers from outside the zone — and reports machine idle time to the owner each morning. Leave an email or phone in the form below.

FAQ

Is PESO approval mandatory for a CCTV camera in a hazardous area? Where the Petroleum Rules apply, PESO's position is yes: its FAQ says all electrical equipment in hazardous areas under those Rules must be approved by the Chief Controller, including imported equipment.

Can an ATEX-certified camera be used in an Indian Zone 1 area? Not on the ATEX certificate alone in petroleum areas. The maker or its Indian service provider must obtain PESO approval, which relies on that IECEx or EU certification.

What is the difference between Ex d and Ex e? Ex d (flameproof) contains an internal ignition; Ex e (increased safety) prevents arcs, sparks and hot surfaces. Since the 2024 amendment, Rule 106 lists both for Zone 1, subject to the EPL (eb = Gb, ec = Gc only).

Last verified 13 Oct 2026 against the vendor and regulator documents listed above. Found an error? Tell Mama in the form below.

Read next
Free · no obligation

Get a camera plan for your floor

Tell Mama about your plant and Mama will come back with how many cameras you need, where they go, and the retention your state expects — sized to your floor, in ₹. Built for Indian factories.

  • How many cameras & exact placement
  • Compliance-ready (BIS/STQC, women's night shift)
  • Honest ₹ estimate — guard vs camera-AI

Mama replies by email or phone — whichever you left. No spam, no obligation.