mama Get a free camera plan ☰
Fire in a Cotton Godown or Garment Unit: The 10-Minute Walk an Owner Should Do

Fire in a Cotton Godown or Garment Unit: The 10-Minute Walk an Owner Should Do

By The Mama Editorial Team · Factory-floor cameras, India compliance & operations

What should a garment or textile owner check on foot to keep a godown fire from starting or spreading? Seven stops in about 10 minutes: the godown door, stack height, aisles, lights and wiring, lint, smoking and heat, then exits and extinguishers. Each stop below quotes the clause in NBC 2016 Part 4 or the BIS fire-safety codes for storage, textile mills and extinguishers, read on 17 Oct 2026.

Last checked: 17 Oct 2026. By the Mama Editorial Team. Code lines quote the primary text; rupee figures are sourced or labelled assumptions.

Key takeaways

Why a separate walk for cotton and cloth

The machine shop safety walk is about cylinders, chips and guards. Cotton and fabric burn differently: fire runs along lint and smoulders inside bales.

The foreword of IS 3079 : 1990, the BIS code of practice for fire safety of cotton textile mills, names the main causes, among them electrical failure, friction and "excessive quantity of fly".

That standard was written for mills, but a garment unit's godown and cutting room hold the same fibre, so this page uses its godown and housekeeping clauses as a reference point.

On 8 December 2019 a fire in a four-storey bag factory in Delhi's Anaj Mandi area killed 43 workers, BBC News reported the same day; at least 100 people had been sleeping inside, and a local fire chief said the building "did not have a proper fire licence".

How your floor is classified

NBC 2016 Part 4, clause 3.1.8, splits industrial buildings into G-1 (low), G-2 (moderate) and G-3 (high hazard). The Authority decides the class "on the basis of the fire loads of the contents".

Area in a textile or garment unit NBC 2016 Part 4, Annex B Max travel distance to an exit (m), construction Types 1–2, Table 5
Sewing floor ("Garment Makers") Moderate hazard 45.0 (G-1, G-2)
Hosiery, embroidery, thread Moderate hazard 45.0
Textile mills Moderate hazard 45.0
Godown storing combustible goods High hazard (sub-category A) 22.5 (G-3) or 30.0 (Group H storage)
Cotton waste factory High hazard (sub-category A) 22.5

Note 1 to Table 5 allows 50% more travel distance in a fully sprinklered building. BIS describes NBC 2016 as a model code "for adoption"; how much of it applies to you depends on your state's fire rules and municipal bye-laws; the BIS codes quoted below are codes of practice written with "should", not statutes.

The walk at a glance

# Where you stand What you look for Clause Time (min)
1 Godown door, outside Nothing parked or stacked in front; hydrant points clear; main switch at the entrance IS 3594 cl. 8.2, 14.9, 11.1.1 1
2 Inside the godown Stack below the painted height band; 1 m from beams and walls IS 3594 cl. 9.2.2.1; IS 3079 cl. 13.2.3, 13.2.6 2
3 Aisles between stacks 2 m wide, kept clear; nothing within 2 m of doors and windows IS 3594 cl. 9.2.1.2–9.2.1.5; IS 3079 cl. 13.2.5 1.5
4 Lights, switches, extension leads Fittings clear of the stack top; switchgear outside the godown IS 3594 cl. 11.2.2–11.2.3.1; IS 3079 cl. 10.5 1.5
5 Cutting room and sewing lines Lint under machines and on beams; waste in closed bins IS 3079 cl. 13.3.10, 13.3.13 1.5
6 Behind the stacks, at the gate No butts, no naked flame or welding, no vehicle with engine running IS 3594 cl. 14.1(b), 14.2, 14.4; IS 3079 cl. 13.3.1 1
7 Exits, stairs and extinguishers Exits unlocked, openable without a key, no bundles in the way; extinguisher in place, visible, within 15 m, gauge in range NBC Part 4 cl. 4.2.3, 4.4.2.4.1(c), 6.8.1.2; IS 2190 Table 1, cl. 11.5 1.5

Stops 1 to 3: the godown

Outside the door. IS 3594 : 1991, the BIS fire code for general storage and warehousing, says no outdoor storage should be allowed within 6 m of a godown "obstructing any access to the building" (clause 8.2). Clause 14.9 bars even temporary storage that blocks doors, hydrant points or sprinkler valves.

Clause 11.1.1 asks for "a main switch with indicator lamp" near the entrance, so power can be cut in a fire.

Stack height. IS 3079 clause 13.2.3: the maximum height of cotton or cloth bales "should not exceed six meters or up to a level which is one metre below the roof, whichever is less".

IS 3594 clause 9.2.2.1 sets a general limit of 4.5 m where no automatic sprinklers are installed. It keeps at least 1.0 m between the stack top and the lowest beam, and asks for a colour band painted on the wall "indicating the maximum height to which materials are to be stacked".

Fully pressed bales should sit at least 1 m from the walls (IS 3079 cl. 13.2.6), never on combustible dunnage such as rice husk (cl. 13.2.4).

Aisles. IS 3594 asks for aisles at least 2.0 m wide, 2.5 m where forklifts work (cl. 9.2.1.3–9.2.1.4), and, for baled fibres, no more than 15 m apart (cl. 9.2.1.2).

IS 3079 is stricter for cotton: passageways "not less than two metres wide and not more than ten metres apart" (cl. 13.2.5). IS 3594 clause 9.2.1.5 keeps goods 2.0 m from doors and windows, so hoses can reach the stack.

Stop 4: lights, switches and loose wiring

For godowns storing fibrous goods, IS 3594 clause 11.2.2 says all switches and control equipment "should be located outside the godown" and portable lamps should be 24 V. Clause 11.2.1 asks for wiring in screwed steel conduit or mineral-insulated cable.

Clauses 11.2.3 and 11.2.3.1 keep light fittings no more than 45 cm below the roof and at least 75 cm clear of the highest stack. IS 3079 clause 10.5 adds a detail any garment owner can check in a minute. Where tube lights are used, wire netting goes below the chokes "so that burning chokes may not fall down to start a fire involving cotton fluffs/loose cotton".

Look for what is not on the drawing: an extension board on a bale, a festival light string, a heater in the checking room.

Stop 5: lint, waste and the cutting room

IS 3079 clause 13.3.13 says loose cotton "from under and around machinery should be cleaned constantly" into self-closing waste bins. Clause 13.3.10 asks for roof and structural members to be cleaned "at least twice in a month".

On a sewing floor, look up at the beams and fittings over the cutting tables, then down at the waste under each line: closed bin, or open heap? IS 3594 clause 14.5 says godowns should be "swept clean everyday".

Stop 6: smoking, heat and vehicles

IS 3594 clause 14.1(b) asks for a displayed notice prohibiting smoking except in selected buildings. Clause 14.2 keeps naked flames, welding, cutting and spray painting to "detached buildings specifically set apart for those purposes".

IS 3079 clause 13.3.1 allows smoking only in a separate enclosed, dust-proof area. Look behind the stacks and outside the godown door for butts.

No vehicle should stand inside a godown with its engine running (IS 3594 cl. 14.4).

Stop 7: exits, then extinguishers

Exits. NBC 2016 Part 4 clause 4.2.3: every exit "shall be continuously maintained free of all obstructions or impediments to full use in the case of fire". Clause 4.4.2.4.1(c) requires exit doors to be operable from the side they serve "without the use of a key".

For storage areas over 1,400 m², or with more than 10 people normally present, clause 6.8.1.2 asks for at least two exit access doors that "shall not be subject to locking so long as any persons are inside".

Extinguishers. IS 2190 : 2010 Table 1 sets the maximum travel distance to an extinguisher at 15 m for light, ordinary and extra hazard alike. The floor area per unit of Class A rating drops from 140 m² (ordinary hazard) to 90 m² (extra hazard).

Clause 11.5 lists what a periodic check covers, including "no obstruction to access or visibility"; clause 11.12 asks for inspection "at least once a month" by trained persons. IS 3079 clause 11.2 says sprinklers "should be installed" in cotton godowns.

What a missed walk costs: a worked ₹ example

Assume a 300-worker home-textile and garment unit in Panipat, Haryana. A short circuit in the godown burns part of the fabric stock and the sewing floor stops for 10 days.

Assume ₹650 a day for a semi-skilled worker (illustrative). Take the current notification for your trade and zone from your state labour department (Haryana Labour Department). Everything else is an assumption too.

Line Basis Amount (₹)
Stock in the godown (assumed) Fabric and trims at cost 2,00,00,000
Stock destroyed (assumed) 25% of the godown 50,00,000
Wages paid while idle 300 workers (assumed all semi-skilled) × ₹650 × 10 days 19,50,000
Contribution lost (assumed) ₹2.5 lakh a day × 10 days 25,00,000
Stock loss not paid because of underinsurance (assumed) ₹50 lakh × (1 − 70% sum insured) 15,00,000
Out of pocket, before any fine Wages + contribution + uninsured stock 59,50,000

It assumes wages are paid during the stoppage and there is no business-interruption cover.

A short note on underinsurance. Insurers pay in proportion when the sum insured is below the value at risk. In the New India Bharat Laghu Udyam Suraksha Policy wording (UIN IRDAN190RP0012V02202021, for ₹5–50 crore at one location), Clause F says underinsurance "will reduce proportionate to the difference" what the insurer pays. It is waived "upto 15%"; below 85% of the value, "You will bear a proportionate share of the loss" (New India policy wording). The table's 70% proportion only shows the size of the gap; the surveyor decides the real figure. See also what insurers ask about CCTV.

On foot or on camera

Stop A fixed camera can show Only a person on foot can check
Aisles Bundles left in the aisle, how often and how long Width with a tape
Lint Heaps under a line, if the angle is low Lint on beams and fittings
Exits Bundles or a trolley against an exit door Door locked, or will not open
Extinguishers Missing, or blocked by stock Gauge, seal, date

Cameras show patterns, such as an aisle blocked every afternoon; see fire and emergency exit monitoring with cameras. Lint also clogs the cameras themselves: what Tirupur's lint does to cameras.

Limits of this walk

The walk does not replace the fire service's inspection, licensed servicing of extinguishers, hydrants and sprinklers, or an electrical audit. It cannot see inside a bale.

Editions read: IS 3594 : 1991 (reaffirmed 2010), IS 3079 : 1990, IS 2190 : 2010. In NBC 2016 Part 4 no clause was found that fixes how often an owner must walk the godown (full text searched, checked 17 Oct 2026). IS 3594 clause 14.6 asks only that every godown be "thoroughly inspected before it is closed", and if possible reinspected one hour later.

The walk checks conditions, not people. Footage of recognisable workers is personal data under s.2(t) of the DPDP Act, 2023; tell workers in writing what is recorded and why (see the worker CCTV notice under DPDP).

Where Mama fits

Mama reads the cameras a plant already has and every morning sends the owner a short plain-language note on where hours and output leaked yesterday, counting machines and flows, not people. A line that stops because bundles block the aisle shows up first as lost hours. Leave an email or phone in the form below.

FAQ

How high can cotton or cloth bales be stacked in a godown? IS 3079 : 1990 clause 13.2.3 says not more than 6 m, or 1 m below the roof, whichever is less. IS 3594 sets 4.5 m for general stacks without sprinklers.

Is a garment unit high hazard under the National Building Code? NBC 2016 Part 4, Annex B lists "Garment Makers" as moderate hazard. Godowns storing combustible goods are high hazard, and under clause 3.1.8 the most hazardous area governs unless it is segregated or protected.

How far should a worker walk to reach a fire extinguisher? IS 2190 : 2010 Table 1 sets a maximum travel distance of 15 m to an extinguisher for every hazard class.

Can the godown door be locked during the shift? NBC 2016 Part 4 clause 6.8.1.2 says exit access doors from storage areas over 1,400 m², or with more than 10 people normally present, "shall not be subject to locking so long as any persons are inside".

Read next
Free · no obligation

Get a camera plan for your floor

Tell Mama about your plant and Mama will come back with how many cameras you need, where they go, and the retention your state expects — sized to your floor, in ₹. Built for Indian factories.

  • How many cameras & exact placement
  • Compliance-ready (BIS/STQC, women's night shift)
  • Honest ₹ estimate — guard vs camera-AI

Mama replies by email or phone — whichever you left. No spam, no obligation.